Skip to main content

Plastic Fabricators

How to Select a Canopy Hood for Industrial Fume Extraction

To choose a canopy hood that will be used to extract industrial fumes, it is important to consider the source of the fumes, heat production, nature of contaminants, hood size, capture distance, airflow requirements, ducting system, and blower capacity. In some cases, the use of a canopy hood may be considered appropriate if fumes, vapor, or heated air rises from the source and is extracted above it. But it does not work for all kinds of dangerous emissions, especially those that are likely to penetrate the breathing zone of the worker.

Canopy hoods are often used in industries, chemical plants, laboratories, workshops, plating, and other locations where fumes, heat, or vapor should be captured.

Choosing the wrong hood will lead to inefficient capture of contaminants, high electricity costs, poor ventilation, and unnecessary exposure to dangerous substances in the air.

The following is a guide on how to choose a canopy hood for industrial fume extraction.

What Is an Industrial Canopy Hood?

Industrial canopy hood refers to a ventilation hood which is mounted above a process, equipment or emission source with a view of capturing the rising contaminants such as fumes, vapors, heat and others.

Usually, the way it operates is by capturing contaminants which tend to rise due to buoyancy or movement of air resulting from the process and channeling them into an exhaust duct.

Some of the components of an industrial canopy hood include:

  • Hood body/ enclosure for collecting contaminants
  • Exhaust opening/ exhaust ducting
  • Supports/mounting for mounting the hood
  • Damper (optional)
  • Exhaust ducting
  • Ventilation/blower

Considerations for use of canopy hoods include:

  • Hot process equipment
  • Certain industrial heating processes
  • Processes that generate steam
  • Open tank processes where vapors rise
  • Heating or cooking processes in industrial settings
  • Certain laboratory or process ventilation processes

Note: Canopy hoods may not be suitable for toxic, dangerous, or worker level emissions. In cases where contaminants can move laterally, enter the breathing zone, or are emitted without upward motion, an enclosed hood or exhaust ventilation system would be better.

1. Identify the Type of Fumes or Emissions

Prior to choosing the canopy hood, determine what exactly needs to be removed.

Industrial operations produce various forms of airborne pollutants; the material of the hood and the extraction mechanism should be suited to the emissions produced.

Consider the following:

In the case of chemical uses, give the chemical name, concentrations, process temperatures, and the conditions of exposure to the hood manufacturer or ventilation expert.

In the case of emission of gases or vapors that are dangerous, find out whether there is need for scrubbing, filtration or some other process before venting.

2. Choose the Right Canopy Hood Design

The hood design should match the process layout, emission source, available space, and capture requirements.

A. Standard Canopy Hood

A normal canopy hood is installed above the process or equipment from which emissions emanate upwards.

This would be applicable where:

  • The emissions tend to rise naturally.
  • The source is positioned below the hood.
  • There is no horizontal motion of contaminants generated by the process.
  • The hood is positioned far enough from the source.
  • The ventilation system can collect the emissions without any risk to personnel.

B. Canopy Hood with Damper

A canopy hood which has a damper provides the ability to control the flow rate into the exhaust ventilation system.

The damper setup can be used for air balancing or isolation purposes, depending upon the system design.

But having a damper in the system does not necessarily mean that you will have better capture efficiency.

Explore Ducting and Canopy Hoods with Damper from Plastic Fabricators for product information.

C. Custom Industrial Canopy Hood

Custom hoods can be provided if the process involves any of the following:

  • Custom hood sizes.
  • Custom duct connection arrangements.
  • Custom installation spacing.
  • Custom material requirements.
  • Custom mounting arrangements.
  • Existing system integration.

Any customisation must be made according to process specifications and ventilation designs.

3. Select the Correct Hood Material

Selecting appropriate materials is a critical decision when selecting a canopy hood for use in an industry for fume removal.

The canopy hood should be able to resist the chemical contact, temperature, humidity, mechanics, and service environment.

PP Canopy Hood

PP Canopy hoods are sometimes specified in chemical environments where polypropylene is compatible with chemicals.

Examples include some acid and caustic fume exhausts depending on the chemicals, their concentration, temperature, and period of exposure.

FRP Canopy Hood

FRP Canopy Hoods can be fabricated by using various types of resins and reinforcing mechanisms.

They might prove useful for use in industrial areas where corrosion protection is required and custom design is needed.

It becomes imperative that the resin system is chosen depending upon the chemicals used.

How to Choose Between PP and FRP?

Do not choose PP or FRP depending on the chemical nomenclature alone.

Think about:

  • Chemical concentration
  • Operating temperature
  • Length of time of exposure
  • Mechanical needs
  • Size of hood
  • Fabrication needs
  • UV exposure if applicable
  • Expected maintenance conditions

The right choice of material needs to be verified according to the process conditions.

4. Determine the Correct Hood Size

The hood should be of sufficient size to accommodate the emissions from the source under the conditions of operation.

Some of the key factors include:

  • Hood length
  • Hood width
  • Hood height/depth
  • Distance between the hood and the source of emissions
  • Exhaust pipe diameter
  • Location of the hood in relation to the machinery

Why Hood Size Matters

A hood that is too small will be unable to capture the emissions emitted through the side gaps.

Hood installed too high above the emissions source will need more air flow and might also perform poorly in capture.

An overly large hood will make the air flow requirement, duct and blower work harder.

Practical Selection Example

Suppose an industrial process tank produces rising fumes from its surface.

Canopy Hood Design Considerations

  • Canopy Hood
  • The canopy hood is intended to encompass the necessary emission area taking into consideration:
  • Dimensions of the Tank
  • Characteristics of Fume Discharge
  • Process Temperature
  • Distance between Hood and Source of Emission
  • Cross Draft due to Doors or Fans
  • Position of Workers
  • Exhaust Air Volume Needed

Dimensioning shall be done by Ventilation Design not based on Tank Dimensioning.

5. Calculate the Required Airflow

Air flow is among the most critical parameters in fume extraction at industries.

The air flow needed will depend on factors like the source of emission, hood design, capture distance, the behavior of contaminants, and the conditions of air flow around the hood.

Some of the cases where canopy hood will need high air flow include:

  • It is far from the source.
  • The source area is large.
  • There is cross flow affecting capture.
  • There is thermal or processed air flow from the source.

Basic Airflow Relationship

For a duct carrying air at a known average velocity:

[
Q=A\times V
]

Where:

  • (Q) = volumetric airflow
  • (A) = duct cross-sectional area
  • (V) = average air velocity

For a circular duct:

[
A=\frac{\pi D^2}{4}
]

Where (D) is the internal duct diameter.

For instance, if the diameter of the duct and velocity to be achieved are known, one may calculate the airflow using the above equation.

This equation is used to determine the airflow passing through the duct only and not the required hood airflow.

Airflow through the hood should be determined by the hood design criteria. For hazardous fumes, ensure that you consult a qualified ventilation engineer.

6. Check Hood-to-Source Distance

The distance between the canopy hood and the emissions source is highly influential in terms of capturing efficiency.

With increased distance, contaminants can be dispersed and can be influenced by ambient airflow.

A canopy hood that is positioned too high could cause escaping of contaminants before getting captured by the hood.

 

Factors to Consider

  • Elevation of the emission source
  • Height at which hood is mounted
  • The thermal rise of the emissions
  • Process air flow
  • Movement of the worker
  • Nearby fans or ventilations
  • Doors and windows
  • Air currents

Where feasible, the hood should be positioned close enough to the source without hindering process operations or worker access.

 

In cases of harmful emissions, refrain from using a canopy hood in situations where the contaminants pass through the breathing zone prior to reaching the hood.

7. Select the Right Ducting Arrangement

Ducting is used to channel the collected emissions from the hood to the blower, scrubber, filter, or vent point.

Ducting is chosen based on:

  • Flow rate
  • Diameter/dimensions of the ducting
  • Air velocity
  • Pressure drops
  • Compatibility of chemicals
  • Temperature
  • Distance to travel
  • Number of bends
  • Number of branches

PP and FRP Industrial Ducting

PP and FRP ducts can be selected for corrosive exhaust systems where there can be a material compatibility.

Material of the duct should have compatibility with emissions from the whole system, including the hood, ducts, blower, and treatment equipment.

Don’t make your choice of duct diameter only on the basis of the diameter of the hood opening.

The entire exhaust system should be analyzed for air flow and pressure loss.

8. Choose the Correct Exhaust Blower

The exhaust blower furnishes the necessary pressure to make the air flow through the hood, ductwork, treatment device, and the discharge system.

A blower must be chosen taking into account the needed air flow and total system static pressure.

Factors to Consider

  • Air flow requirement
  • Total pressure loss of the system
  • Length and diameter of ductwork
  • Number of bends and fittings
  • Pressure loss across scrubber or filter
  • Temperature of emission
  • Chemical resistance
  • Material of the blower
  • Operating conditions
  • Drive system

Why Blower Selection Matters

The smaller blower may not provide adequate flow.

The larger blower may waste energy and create excess flow and noise.

The appropriate size should be determined by the operation point and performance curve of the manufacturer.

For chemical exhaust systems, material compatibility and proper blower construction are especially important.

Explore the Direct Drive Blower and Indirectly Driven Blower for Exhaust Scrubbing product pages from Plastic Fabricators.

9. Should You Connect a Canopy Hood to an Industrial Scrubber?

In some industrial processes, it might be necessary to treat the captured air prior to its emission.

Scrubbing technology may be applied where there are pollutants in the exhaust gases that could be effectively controlled via the chosen treatment method.

The choice of the treatment technology depends on the nature of the pollutant.

Examples are as follows:

  • Specific acid gases may need specific scrubbing technology.
  • Alkaline gases may need some specific treatment technology.
  • Particulate emissions may need particle control technologies.
  • Mixed emissions may need a combination of different treatment processes.

Scrubbing technology should be based on the pollutant, its concentration, airflow, temperature, etc.

 

A canopy hood alone does not remove pollutants from the exhaust. It captures and conveys emissions; treatment and discharge control are separate functions.

For industrial applications, explore PP/FRP Scrubber Systems from Plastic Fabricators.

10. Installation and Maintenance Considerations

Even a well-chosen canopy hood may function poorly when it is improperly installed and maintained.

Installation Requirements

  • Install the hood following the ventilation design.
  • Maintain the proper spacing between the hood and source.
  • Inspect duct joints for leaks.
  • Inspect the direction of rotation and functionality of the blower.
  • Inspect the flow rate.
  • Balance the system as needed.
  • Inspection of the damper.
  • Inspection of the exhaust discharge arrangement.
  • Prevent interference from nearby fans or air supply openings.

Maintenance Checklist

Component What to Inspect
Hood Cracks, corrosion, physical damage, and contamination
Ducting Leaks, deposits, corrosion, and damaged joints
Damper Movement, position, and operating condition
Blower Vibration, noise, performance, and mechanical condition
Scrubber Pressure drop, liquid circulation, and treatment performance where applicable
Connections Loose fasteners and damaged supports
System airflow Whether required operating conditions are maintained

Inspection frequency should be based on the process, hazard level, operating conditions, and applicable requirements.

Why Consider Plastic Fabricators for Industrial Canopy Hoods?

Plastic Fabricators provides industrial ducting and canopy hoods that need to have the right materials chosen and fabricated for the job.

Depending on the situation, the buyer can talk about:

  • FRP or PP canopy hood specifications
  • Specific hood dimensions
  • Duct connection
  • Damper specification
  • Material compatibility
  • Industrial exhaust ventilation specifications
  • Scrubber/blower integration

Explore the Ducting and Canopy Hoods with Damper product page to learn more about the available product range.

For a quotation, provide the emission source details, process temperature, hood dimensions, duct layout, material requirements, and installation conditions.

Conclusion

Selecting an appropriate canopy hood for fume extraction from industries needs more than just selecting the size and material of the hood.

It depends on many factors including the source of emission, the properties of contaminants, the distance between the hood and the emission source, required air flow, ductwork layout, blower capacity, material compatibility, and requirement of exhaust treatment.

An appropriate canopy hood design can facilitate the capture of rising emissions from industries, but it should be selected as per the process and its proper placement to avoid the escape of contaminants into the breathing zone of the workers.

For corrosive industrial applications, PP and FRP canopy hoods may be an option provided that the material specifications are appropriate for the actual process.

Prior to ordering, verify all specifications of the canopy hood including the size, material, duct fitting, air flow, and installation layout.

To discuss industrial canopy hood requirements, visit the Plastic Fabricators Canopy Hoods and Ducting page.